Experiment 02

The accessibility ramp

The wheelchair ramp between a street and a building entrance. A different subject from the car ramp, with its own source and its own numbers; the rules of one are never applied to the other.

01Slope

Slope is a ratio, and the gentler it is the longer the ramp

Slopes here are written as ratios: 1 to a number. The steepest allowed is 1:12.

For a level difference of 0.45 m at 1:12: one run of 5.40 m and a landing of 1.80 m at each end, 9.00 m in all.

Try itChange the slope, and drag the entrance level.

Slope
0.45 m

02Runs

A higher entrance breaks into runs

A single run may not rise more than 0.75 m, and may not be longer than the length given for its slope: 9.00 m at 1:12, 12.00 m at 1:16, and 15.00 m at 1:20.

So a higher entrance is reached by several runs separated by level landings: one at the bottom, one at the top, and one between every two runs. The number of landings is the number of runs plus one.

For a level difference of 3.00 m at 1:12: 4 runs of 9.00 m each, 5 landings, 45.00 m in all.

Try itRaise the entrance level, and watch the available length.

0.45 m
12.00 m

03Width

Width, handrails and edge protection

The minimum width follows the building: 1.50 m for a public building, 0.90 m for shared residential, 0.80 m for a single dwelling. A landing is at least as wide as the ramp.

When the ramp rises more than 0.60 m, handrails are required: between 0.84 m and 1.00 m high, extending 0.30 m beyond each end. Edge protection is at least 0.05 m with handrails and 0.075 m without.

Try itChange the width and the building type.

Building type
1.50 m

The wheelchair-user outline in the drawing is 1.10 m × 1.35 m, for illustration only, and is unverified.

About the numbers

The following values are from the Jordanian building requirements code for persons with disabilities, Jordan National Building Council.

Steepest slope allowed
1:12
Maximum rise of a single run
0.75 m
Maximum run length by slope
1:12 → 9.00 m · 1:16 → 12.00 m · 1:20 → 15.00 m
Minimum landing length
1.80 m
Minimum width: public building, shared residential, single dwelling
1.50 m · 0.90 m · 0.80 m
Handrails required when the rise is more than
0.60 m
Handrail height
0.84–1.00 m
Handrail extension beyond each end
0.30 m
Edge protection: with handrails, and without
0.05 m · 0.075 m

Working values, unverified

The wheelchair-user outline in the drawing is for illustration only and is not from the source.

Wheelchair-user outline
1.10 × 1.35 m ◊

In the same source, and not calculated here

  • Handrails on one side or both, depending on width and slope.
  • Corridor slopes and widths.
  • Kerb ramps at pavements.
  • Temporary ramps.
  • Landings at changes of direction: the experiment designs a straight ramp only.

This is an experiment for explanation. It does not replace the governing code or the design engineer.